Calculate variable speed pump energy savings with the hours your system spends at each operating point and the electrical input power at those points. A duty profile makes it possible to compare equipment that uses similar power at peak load but behaves differently for most of the year.
What the pump affinity laws can tell you
For comparable operating conditions on the same centrifugal pump and impeller, flow scales with speed, head with speed squared, and shaft power approximately with speed cubed. At 80% speed, that idealised power ratio is 0.8³, or about 51%. System static head, changes in efficiency, and drive and motor losses affect actual electrical input. The U.S. Department of Energy operations and maintenance guide discusses affinity laws and variable-speed operation.
Build an annual duty profile
- Use plant logs or measurements to estimate annual hours at high, medium and low demand.
- Get the electrical input power for the baseline and candidate at the same useful duty. Use consistent measurement boundaries and state whether drive losses are included.
- Multiply each power value in kilowatts by its annual operating hours, then add the totals to obtain annual kWh.
- Subtract proposed use from baseline use. If estimating annual cost savings, apply the applicable energy rate and model demand charges separately when relevant.
Worked example using illustrative power readings
| Demand | Annual hours | Baseline input | Variable-speed input |
|---|---|---|---|
| High | 1,000 | 20 kW | 20 kW |
| Medium | 2,000 | 18 kW | 13 kW |
| Low | 1,000 | 16 kW | 9 kW |
The baseline uses 72,000 kWh a year. The variable-speed case uses 55,000 kWh. The illustrative saving is 17,000 kWh a year, or 23.6%. The calculation assumes that both options supply the same required service in each demand band.
What to check before using the number in a proposal
- Use the system curve and static head to confirm that the reduced speed still delivers required flow and pressure.
- Check efficiency and the manufacturer’s minimum operating limits across the proposed range.
- Review staging if the installation uses multiple pumps. Test low and peak demand separately.
- Compare modelled input power with measured input during acceptance testing, using equivalent operating conditions.
Use Velotech’s guides to compare centrifugal pump curves and assess parallel pump selection guide. For measurement planning, see the guide to pump testing software and PLC automation.